sns share

Meta-MEC MCCB&ELCB Series

Characteristics

Characteristics

Meta-MEC MCCBs shall comply with IEC 947-1 and 947-2 standards or with the corresponding standards applicable in the member countries (EN 60 947-1, 2)

Suitable for isolation, as defined by IEC 947-2

  • - Line protection
  • - Motor/generator protection
  • - Starter combination
  • - Offering economical solution with compact sizes and increased interrupting capacities.
  • - Complete range of two, three and four-pole version.
  • - Employing a fixed thermal and fixed magnetic trip.
  • - Rating plugs to change thermal currents are available for 400 and 800AF.
  • - 3-pole ELCBs physically interchangeable with 3-pole MCCBs are available.
  • - Offering more accessories such as rear connection and extended rotary type handles.
  • - Frames made of rigid materials of engineering plastics.
  • - 400, 800AF breakers use the individual rating plug for determining the continuous current rating.
  • - MCCB with reference temperature 50℃ is available on request.
  • - Motor protection MCCBs with magnetic only trip are available.

Ratings

Ratings

Simplified four frames
AF Poles Type Rated current (A), In Ulitimate breaking capacity (kA rms), Icu
220V 460V
50 2 ABE 52b 5, 10, 15, 20, 30, 40, 50 10 5
3 ABE 53b
60 2 ABE 62b 60 10 5
3 ABE 63b
100 2 ABE 102b 5, 10, 15, 20, 30, 40, 50, 60, 75, 100 25 10
3 ABE 103b
4 ABE 104b
225 2 ABE 202b 100, 125, 150, 175, 200, 225 35 18
3 ABE 203b
4 ABE 204b
400 2 ABE 402b 250, 300, 350, 400 35 25
3 ABE 403b
4 ABE 404b
800 2 ABE 802b 500, 600, 630, 700, 800 50 35
3 ABE 803b
4 ABE 804b
30 2 ABS 32 5, 10, 15, 20, 30 10 5
3 ABS 33
50 2 ABS 52b 5, 10, 15, 20, 30, 40, 50 25 10
3 ABS 53b
4 ABS 54b
60 2 ABS 62b 60 25 10
3 ABS 63b
4 ABS 64b
100 2 ABS 102b 15, 20, 30, 40, 50, 60, 75, 100 50 25
3 ABS 103b
4 ABS 104b
225 2 ABS 202b 100, 125, 150, 175, 200, 225 50 25
3 ABS 203b
4 ABS 204b
400 2 ABS 402b 250, 300, 350, 400 50 35
3 ABS 403b
4 ABS 404b
800 2 ABS 802b 500, 600, 630, 700, 800 100 50
3 ABS 803b
4 ABS 804b
1200 3 ABS 1003 1000 100 65
4 ABS 1004
3 ABS 1203 1200 100 65
4 ABS 1204
Simplified four frames
AF Poles Type Rated current (A), In Ulitimate breaking capacity (kA rms), Icu
220V 460V
30 2 ABH 32b 5, 10, 15, 20, 30 25 10
3 ABH 33b
50 2 ABH 52b 15, 20, 30, 40, 50 50 25
3 ABH 53b
4 ABH 54b
100 2 ABH 102b 15, 20, 30, 40, 50, 60, 75, 100 65 35
3 ABH 103b
4 ABH 104b
225 2 ABH 202b 100, 125, 150, 175, 200, 225 65 35
3 ABH 203b
4 ABH 204b
400 2 ABH 402b 250, 300, 350, 400 85 50
3 ABH 403b
4 ABH 404b
50 2 ABL 52a 15, 20, 30,40, 50 100 65
3 ABL 53a
4 ABL 54a
100 2 ABL 102a 15, 20, 30, 40, 50, 60, 75, 100 100 65
3 ABL 103a
4 ABL 104a
225 2 ABL 202a 100, 125, 150, 175, 200, 225 125 65
3 ABL 203a
4 ABL 204a
400 2 ABL 402b 250, 300, 350, 400 125 85
3 ABL 403b
4 ABL 404b
800 2 ABL 802b 500, 600, 630, 700, 800 125 85
3 ABL 803b
4 ABL 804b
Simplified four frames
AF Poles Type Rated current (A) Adjustable current Ulitimate breaking capacity (kA rms), Icu Operating characteristics
AC220V AC460V Long time(A,Ir) Short time(A,Im) Instantaneous(A,It)
1200 3 ABS 1203E 1200 (0.5, 0.6, 0.7, 0.8, 0.9, 1.0)
X In
100 50 (0.5, 0.6, 0.7, 0.8, 0.9, 1.0)
X In
(2, 3, 4, 5, 6, 8, 10)
X In
11 X In

Accessories

Accessories

Electrical Auxiliaries

  • -Auxiliary switch, AX Indicates the "open" or "close" position
  • -Shunt Trip, SHT Remote opening of a circuit breaker
  • -Alarm switch, AL Indicates the "tripped" condition
  • -Under voltage Trip, UVT Opening in the event of a drop in voltage

External accessories

  • -Terminal Cover
  • -Rotary Handle
  • -Rear Connection Unit
  • -Motor operator
  • -Insulation barrier
  • -Mechanical Interlock
  • -Key-locking device
  • -Plug-in Base

Certification

Certification

The products manufactured by LS Industrial Systems Co. satisfy the international standards(IEC). These product standards precisely define the performance of the designed products, such as IEC 947 for low voltage equipments.
We, LS Industrial Systems Co., are able to provide proof of conformity of its production, in accordance with the standards through our quality assurance system.

Applied standard

IEC 60947-2

Approvals & Certifications

  • - CB by KEMA
  • - Approved by marine classification authorities such as LR, ABS, KR
  • - CE marking
  • - CCC

Download

検索
  • Catalog

    太陽光 発電用 電力系統ソリューション

    2017.11.13 Japanese 27MB

    太陽光 発電用 電力系統ソリューション

    Certification

    [ACB]Susol Series Certification

    2011.02.24 English

    KS 1.AH-06~16, 20D AH-20~32E, 40E AS-40~50G, 63G CE 2.AH-06~16, 20D AH-20~32E, 40E AS-40~50G, 63G GOST 3.AH-06~16, 20D AH-20~32E, 40E AS-40~50G, 63G KEMA 4.AH-06~16, 20D 5.AH-20~32, 40E 6.AS-40~50, 63G

  • Certification

    [ACB]Susol Series Marine classification

    2011.02.24 English

    LR 1.AH-06~16D, 20D AH-20~32E, 40E AH-40~50G, 63G BV 2.AH-06~16D, 20D AH-20~32E, 40E AH-40~50G, 63G ABS 3.AH-06~16D, 20D AH-20~32E, 40E AH-40~50G, 63G DNV 4.AH-06~16D, 20D AH-20~32E, 40E AH-40~50G, 63G

    Certification

    [ACB]Metasol Series Certification

    2011.02.24 English

    KS 1.AN-06~16D AS-06~16D, 20D AN-20~32E AS-20~32E, 40E AS-40~50F AS-40~50G, 63G KEPIC 2.AS-40~50F CE 3.AN-06~16D AS-06~16D, 20D AN-20~32E AS-20~32E, 40E AS-40~50F AS-40~50G, 63G GOST 4. AN-06~16D AS-06~16D, 20D AN-20~32E AS-20~32E, 40E AS-40~50F AS-40~50G, 63G KERI 5.AS-40~50F KEMA 6. AS-06~16D, 20D 7. AS-20~32E,40E 8. AS-40~50F 9. AS-40~50G,63G

  • Certification

    [ACB]Metasol Series Marine classification

    2011.02.24 English

    KR 1.AS-06~16D, 20D AS-20~32E, 40E AS-40~50F AS-40~50G, 63G LR 2. AS-06~16D, 20D AS-20~32E, 40E AS-40~50F AS-40~50G, 63G BV 3.AS-06~16D, 20D AS-20~32E, 40E AS-40~50F AS-40~50G, 63G GL 4.AS-06~16D, 20D ABS 5.AS-06~16D, 20D AS-20~32E, 40E AS-40~50F AS-40~50G, 63G DNV 6.AS-06~16D, 20D AS-20~32E, 40E AS-40~50F AS-40~50G, 63G RINA 7.AS-06~16D, 20D AS-20~32E, 40E AS-40~50F AS-40~50G, 63G NK 8.AS-06~16D, 20D 9.AS-20~32E, 40E 10.AS-40~50F 11.AS-40~50G, 63G 5.

    Catalog

    [MCB] MCB Catalog

    2011.02.22 English 4MB

FAQ

電力ソリュ-ション
グリーンビジネス電力ソリュ-ション自動化ソリュ-ション
Low Voltage
TransformerHVDC/FACTSLow VoltageIntegrated Protection & Monitoring EquipmentMedium VoltageElectronic MeterSwitchgear
MCCB & ELCB
MCB & RCCBMCCB & ELCBAir Circuit BreakersContactor & RelayManual Motor SeriesEMPRSurge Protective Device
Meta-MEC MCCB&ELCB Series
Susol MCCB SeriesMetasol MCCB&ELCB SeriesMeta-MEC MCCB&ELCB SeriesUL Listed MCCBSusol 1600AF MCCB

販売店をご確認ください。

ショートカット
  • Technical Question Meta-MEC MCCB&ELCB Series

    [MCCB] Meta-MEC UL MCCB Tightening torque

  • Technical Question Meta-MEC MCCB&ELCB Series

    [MCCB] MCCB inquiry

    Unfortunately, we don´t have any products appropriate for your inquiries. We´re sorry for unhelpful.
  • Technical Question Meta-MEC MCCB&ELCB Series

    [MCCB] Extensible for MCCB

    Do you mean the rear connection unit for the MCCBs ? Please see the third page of the attached Meta-MEC MCCB leaflet, then you can see the rear connection kits. If you mean the rear connection unit, you can use up to 800A
  • Technical Question Meta-MEC MCCB&ELCB Series

    [MCCB] MCCB TERMINAL

    That is not the rust at all. That is some kind of discoloration. In fact, the plating method between line & load side terminal was some different. But the original material for terminal is same. For the line side terminal, we applied the silver plating. And for the load side terminal, we applied the tin (Sn) plating. The reason why we applied different plating method should we use was because of the conductivity. The discolored period for line side terminal is faster than that of load side because of this different plating method. However, you can use this discolored MCCBs safely because that is not the rust. We have experience to check the quality of discolored MCCBs and there´s no problem founded for quality in use except color. If you want to remove the trace of discolor, you can do it by using an rubber eraser. As we explained above, long time storage can make the discoloration of terminal. However, you can use this discolored MCCBs safely.
  • Technical Question Meta-MEC MCCB&ELCB Series

    [MCCB] Cable Size for MCCB

    The cable size for termination for 400AF is 240mm2 x 1EA and for 800AF is 240mm2 x 2EA. However, we cannot understand the exact meaning of extended terminals. So we wonder if you can use or not these cables for with & without extended terminals
  • Technical Question Meta-MEC MCCB&ELCB Series

    [MCCB] Moulded Case circuit breaker specification

    Well, some kinds of AB/GB type MCCBs employ the silver tungsten contacts but some kinds are not. The material is depends on the ampere range. The other clauses ; such as de-ionizing arc chutes and etc. ; are acceptable.